Air Furnace Gasoil – Gas
GF 3060

Description

  • Stainless steel combustion chamber
  • Can be equipped with thermostatic control system and low fuel consumption
  • High safety by fan limit – control system
  • Delay in fan operating before or after burner on
  • High efficiency centrifugal fan
  • Automatic fan control by heat exchanger temperature
  • Increased reliability pressure relief in the combustion chamber
  • Three-Phase control panel
  • Reduced heat loss with double-wall body insulated with rock wool
  • Warm air flow with supply & return ducts (outside installation- Max:20m)
  • Air quality control and fuel saving with fresh air supply and return ducts (Outdoor Installation)
  • Can be connected to supply and return duct and dual burner (natural gas & gas-oil) available vertically or horizontally
  • Can be ordered vertically standing or horizontally
  • Rust-resistant body with epoxy polyester coating
  • High thermal resistance internal components with silicon coating (up to 450 )
  • Indoor / Outdoor Installation

Additional information

Specifications Unit OF3000 GF3060
Fuel type Gasoil NG
Fuel consumption Per hour 33.3 Lit 32 m³
Heat input kcal/h 300000
Kw 350
Thermal efficiency (Gross) % 77
Heating space (Approx.) 5500 – 8500
Electrical (A, V, ph) 10, 380, 3
Fan type centrifugal
Air flow cfm 12565
m³/h 21360
Dimensions (Indoor or Vertical)
(Height, Length, Width)
cm 310×221×139
Dimensions (Indoor or Outdoor / Horizontal)
(Height, Length, Width)
cm 153×267×221
Dimensions (Indoor or Outdoor / Vertical)
(Height, Length, Width)
cm 277×221×142
Weight (gross) kg 1010
Flue diameter cm 30